CAN (Controller Area Network) is a serial bus system especially suited to structure intelligent industry devices networks and build smart automatic control systems. The I-7565 is a cost-efficient device for coupling the CAN-bus to the PC using the standard USB interface. Nowadays the interface is present in every new PC and is supported by the MS-Windows 98, Me, 2000 and XP operating systems. If you establish the connection between the I-7565 and the PC during the runtime of the computer, the PC automatically loads the relevant device driver (hot plug & play).

The following figure shows the application architecture for I-7565 modules. The PC can be the CAN host, monitor or HMI to access/control the CAN device through the CAN network by the I-7565 Converter. This module let you to communicate with CAN devices easily from PC with USB interface.

3000V isolation on CAN side
The CAN port of I-7565 is an isolated with 3000V isolation. This isolation can protect the local devices from the damage signal coming from CAN network.

Watchdog inside
The I-7565 Watchdog is a hardware reset circuit to monitor the I-7565’s operation status. When working in harsh or noisy environment, the I-7565 may be down by the external signal. The circuit may let the I-7565 to work continuously and never halt.

Power and Error indicator display
There are two indicators on the I-7565.The power indicator can help user to check whether the I-7565 is standby or transmitting/receiving messages. The Error indicator will be turned on when some errors occur on the I-7565.

 
•Factory Automation    
•Building Automation    
•Home Automation    
•Control System    
•Monitor System
•Vehicle Automation



 

The PM-213x-CAN series power meter provides the CAN bus interface for users to easily gather the real-time power consumption information in their CAN applications. The PM-213x-CAN provides the Auto-Response mode which responses messages at regular intervals automatically. It makes the communication more efficient when collecting a lot of remote power information. The polling mode offers the precise information of every step required by the monitors. In addition, the PM-213x-CAN also owns the arbitration mechanism which can avoid data collision and error detection.

Features of CAN bus power meter:
  • NXP TJA1042 CAN transceiver
  • Follow CiA CAN 2.0B specification
  • Support Auto-Response mode and Polling mode
  • Support baud rate 125 kbps, 250 kbps and 500 kbps
  • Support up to 255 nodes on the CAN network
  • 2500 Vrms isolation on CAN port
  • 4 kV ESD protection on CAN port
  • CAN bus provides better capability in noise suppression
  • Support arbitration mechanism to avoid collision
  • Support error detection and error correction on CAN bus
  • RoHs Design
  • Fully compatible with the ISO 11898-2 standard
  • No external power supply is required as I-7565 takes it's power from the USB bus
  • 82C250 CAN transceiver
  • Transmission speed up to 1M bps for CAN and 921.6K bps for USB
  • Support both CAN 2.0A and CAN 2.0B
  • Built-in jumper to select 120 ohm terminal resister
  • Power, data flow and error indicator for CAN and USB
  • 1000 frames in CAN received buffer
  • Watchdog inside
  • Windows 98/ME/2000/XP/Linux drivers support
  • Linux driver supported‥
 
  • CAN bus Baud rate configuration
  • CAN acceptance filter configuration
  • CAN2.0A or 2.0B specific selection
  • Checksum and Error Response settings
  • Easy test to transmit/receive CAN messages
  • It has a CAN message field which can display the receiving CAN messages in Decimal or HEX mode
  • Can display the timestamp of each received CAN message
  • Users can change the display mode, up-down, down-up or stop
  • It can count the number of received CAN messages
  • Data Log : It can save the CAN message as “ txt ” file
  • Has CAN ID filter function
  • Can send CAN message to CAN BUS according the defined interval time

 

There are various communication interfaces among the CAN devices like PCI CAN board, Ethernet series and RS-232 series CAN module. According to different purpose of users’ projects, the users maybe need to choice different CAN products. Because of this situation, the programmer should develop different communication program to handle different CAN device. For example, the user should develop “Socket Client” to communicate with I-7540. When using I-7530, the users need “UART” technique to communicate with it. Nowadays, ICP DAS develop the Virtual CAN technique. The Virtual CAN driver is the excellent tool for users. It transforms whole CAN devices into Virtual CAN port. And then it generates Virtual CAN port like “VxCAN 1” or “VxCAN 2”. The users could send and receive CAN message by appointing the Virtual CAN port number. The users don't need to care about what kind of CAN device which is used.

InduSoft Web Studio is a powerful, integrated collection of automation tools that includes all the building blocks needed to develop modern Human Machine Interfaces (HMI), Supervisory Control and Data Acquisition (SCADA) systems, and embedded instrumentation and control application.

In order to apply the field bus communication by InduSoft software, ICP DAS provides several field bus components such as CAN, CANopen, DeviceNet and so on, in the InduSoft driver. By means of these drivers, you don't need to have the complex and abstruse background of these field bus protocols. Only few simple steps can finish the communication between your PC and the remote devices.

PC Platform File Select
WinXP / Win7 InduSoft CAN Driver (IDCAN) for PC/XPAC-8000 (The InduSoft driver list )
Supported Devices
CAN bus series I-7530, I-7530A, I-7540D, I-7565, I-7565-H1, I-7565-H2, PISO-CAN100U, PISO-CAN200U, PISO-CAN400U, PISO-CAN800U, PEX-CAN200i, PISO-CM100U
CANopen series PISO-CPM100U, I-7565-CPM
DeviceNet series PISO-DNM100U, I-7565-DNM
PAC Platform File Select
XPAC-8000 / XPAC-8000-Atom InduSoft CAN Driver (IDCAN) for PC/XPAC-8000
(The InduSoft driver list )
XPAC-8000-CE6 / XPAC-8000-Atom-CE6 InduSoft CAN Driver (IDCAN) for XPAC-8000-CE6
(The InduSoft driver list )
WinPAC / ViewPAC InduSoft CAN Driver (IDCAN) for WinPAC and ViewPAC
(The InduSoft driver list )
Supported Device
CAN bus series I-8120W
CANopen series I-8123W
DeviceNet series I-8124W
 
Hardware
EEPROM
2 KB (for system information), 100,000 erase/write cycles
CAN Interface
Port Channels
1
Transceiver
Philips 82C250
Connector
9-pin male D-Sub (CAN_L, CAN_SHLD, CAN_H, N/A for others)
Baud Rate
10 k, 20 k, 50 k, 100 k, 125 k, 250 k, 500 k, 800 k and 1 Mbps
Isolation
3000 Vrms on the CAN side
Terminator Resistor
Selectable 120 Ω terminator resistor by jumper
Support Protocol
CAN 2.0A/2.0B
Receive Buffer
1000 data frames
Max Data Flow
250 fps
UART Interface
Connector
USB Type B
Baud Rate
921.6 kbps fixed
Compatibility
USB 1.1 and 2.0 standard
Receive Buffer
900 data frames
Power
Power Consumption
1.5W
LED
Round LED
ON LED: Power and Data Flow; ERR LED: Error
Mechanism
Installation
DIN-Rail
Dimensions
72mm x 112mm x 33mm (W x L x H)
Environment
Operating Temp.
-25℃ to 75℃
Storage Temp.
-30℃ to 80℃
Humidity
10~90% non-condensing
Nach oben